UPS PRIME TOWER 6kVA/6000W LCD with 16 x 12V 7Ah - 1106STB16X7

https://tescom.odoo.cloud.existanze.gr/web/image/product.template/3567/image_1920?unique=5ed64fb

Online Double Conversion UPS with Parallel Capability (Scalable).

The Tescom PRIME 1106STB (6kVA) offers maximum power density (6000W, PF=1.0) and is designed to adapt to the growing needs of your business. It supports parallel operation of up to 4 units, allowing for the immediate increase of the total installation power. With 3-level inverter technology, it ensures high efficiency and energy saving.

  • Power: 6kVA / 6000W (PF 1.0).
  • Scalability: Parallel up to 4 units for power increase.
  • Batteries: Built-in VRLA (16x 12V/7Ah).
  • Technology: Online Double Conversion (DSP & 3-Level Topology).
  • Efficiency: High efficiency >94% (Eco Mode >98%).
  • Connection: Hardwired (Input/Output Terminal).
  • Communication: USB, RS-232, RS-485 & Intelligent Slot.

SKU: UPS.0793

790.00 € 790.0 EUR 790.00 €   Οι τιμές δεν περιλαμβάνουν ΦΠΑ

Not Available For Sale

  • Apparent Power
  • Real Power
  • Form Factor
  • Rated Voltage
  • Voltage Range
  • Rated Frequency
  • Frequency Range
  • Input Power Factor
  • Total Harmonic Distortion (THDi)
  • Output Voltage
  • Voltage Regulation
  • Frequency
  • Output Power Factor
  • Efficiency
  • Waveform
  • Transfer Time
  • Harmonic Distortion (THDv)
  • Parallel Connection
  • Crest Factor
  • Overload Capability
  • Display
  • Hot - Swappable battery
  • Battery DC Voltage
  • Battery Type
  • Battery Number
  • Charging Current
  • Typical Recharge Time
  • Cold Start
  • Full Protection
  • Dimension, D x W x H (mm)
  • Net Weight (kg)
  • Operating Temperature
  • Operating Humidity
  • Altitude
  • IP Rating
  • Noise Level at 1 m
  • Communication Ports

This combination does not exist.

Specifications

01 Capacity
Apparent Power 6 kVA
Real Power 6 kW
02 Form Factor
Form Factor Tower
03 Input
Rated Voltage 208 / 220 / 230 / 240 Vac
Voltage Range 110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 288 Vac (no derating)
Rated Frequency 50 / 60 Hz
Frequency Range 40 ~ 70 Hz
Input Power Factor ≥ 0.99
Total Harmonic Distortion (THDi) ≤ 5%
04 Output
Output Voltage 208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage Regulation ± 1%
Frequency Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
Output Power Factor 1
Efficiency 94% at 100% load | max. 95% at 60% load | 98% in ECO mode
Waveform Pure Sine
Transfer Time 0 ms
Harmonic Distortion (THDv) ≤ 1% (linear load)
Parallel Connection Up to 4 units
Crest Factor 3:1
Overload Capability 105% ~ 110% for 10 min | 110% ~ 125% for 1 min | 126% ~ 150% for 30 s
05 Display
Display LCD
06 Battery
Hot - Swappable battery Yes
Battery DC Voltage 192 Vdc (192 ~ 240 Vdc settable)
Battery Type 7 Ah
Battery Number 16
Charging Current 1 A
Typical Recharge Time Standard model: 90% capacity restored in 8 hours
Cold Start Yes
08 Protection
Full Protection Short-circuit | overload | overtemperature | battery low voltage | overvoltage | undervoltage and fan failure
09 Physical
Dimension, D x W x H (mm) 191x465x711
Net Weight (kg) 53
10 Environment
Operating Temperature 0°C ~ 40°C
Operating Humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m derating 1% for each additional 100 m
IP Rating IP20
Noise Level at 1 m ≤ 50 dB
11 Management
Communication Ports RS232 (standard) | USB, RS485, dry contacts, SNMP, battery temperature compensation (optional)